Bear Customer initially, High-quality first in mind, we work closely with our prospects and supply them with efficient and specialist companies for Dry Sprinkler, Professional Fire Protection Sprinkler, 68 Degree Pendant Spray Fire Sprinkler, Seeing believes! We sincerely welcome the new clients abroad to build organization associations and also hope to consolidate the associations while using the long-established prospects.
PriceList for Glass Bulb Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong Detail:

Size(mm) Temperature Rating (℃/°F) Color
A 2.4 68℃ / 155°F red
B 1.5 79℃ / 175°F yellow
C <4.2 93℃ / 200°F green
D 3±0.1 141℃ / 286°F blue
d1 3.5±0.4
d2 3.5±0.3
L 23±0.5
l1 20±0.4
l2 19.8±0.4
Glass bulb load(N) Average Cursh load(X) 3600
lower Tolerance Limit(TL) ≥1600
aximum clamping torque 6.5 N·cm
Response time index(m*s)0.5 RTI≤50

kjhgoiuhjkl

The printed text on 3mm sprinkler bulb is “ZJCY”. Compared with 5mm sprinkler bulb, its response will be faster, RTI ≤ 50, where RTI is a coefficient measured under standard conditions to measure the sensitivity of sprinkler bulb. Expressions:RTI= τ u ½

Where: RTI – response time coefficient, unit (m * s) ½;
τ- Response time constant, in S;
u – gas flow rate, unit: M / s
The quality of the sprinkler bulb fully complies with the Chinese national standard GB18428-2010. The diameter of the sprinkler bulb is 3mm, and the deviation from the nominal diameter will not exceed ± 0.1mm; Its length is 23mm and the deviation from the nominal length will not exceed 0.5mm.
The average crushing load of the sprinkler bulb is 3600n. During the test, the sprinkler bulb will be fixed between the supporting elements in an appropriate way, and the supporting elements are made of steel. The Rockwell hardness is (44 ± 6) HRC, which meets the corresponding service requirements. Then, apply a uniform load along the axis of the sprinkler bulb until the sprinkler bulb bursts, and the rate of load increase is (250 ± 25) n / s. The maximum deviation of the equipment used to measure the crushing load shall not exceed ± 1% of the measured value. Use multiple groups of measured data to calculate the average value and standard deviation of the crushing load and judge whether the results meet the specified standards.


Product detail pictures:

PriceList for Glass Bulb Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

PriceList for Glass Bulb Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

PriceList for Glass Bulb Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

PriceList for Glass Bulb Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures


Related Product Guide:

Good quality comes initial; company is foremost; small business is cooperation is our business philosophy which is frequently observed and pursued by our business for PriceList for Glass Bulb Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong , The product will supply to all over the world, such as: Sweden, Sao Paulo, Madrid, Our company insists on the purpose of takes service priority for standard, quality guarantee for the brand, do business in good faith, to offer skilled, rapid, accurate and timely service for you. We welcome old and new customers to negotiate with us. We are going to serve you with all sincerity!
  • This company can be well to meet our needs on product quantity and delivery time, so we always choose them when we have procurement requirements.
    5 Stars By Queena from Costa rica - 2018.05.15 10:52
    We feel easy to cooperate with this company, the supplier is very responsible, thanks.There will be more in-depth cooperation.
    5 Stars By Jean Ascher from Denmark - 2017.05.02 18:28
    Write your message here and send it to us