Fire Fighting Eqiupment ZSTX 15-93℃ Side wall Chrome plated Fast response Fire sprinkler heads – Zhurong
Fire Fighting Eqiupment ZSTX 15-93℃ Side wall Chrome plated Fast response Fire sprinkler heads – Zhurong Detail:
Fire Sprinkler | |
Type | Side wall |
Material | Brass |
Nominal diameter(mm) | DN15 or DN20 |
K factor | 5.6(80) OR 8.0(115) |
Rated Working Pressure | 1.2MPa |
Testing pressure | 3.0MPa holding pressure for 3min |
Sprinkler Bulb | Fast response |
Temperature rating | 93℃(200℉) |
What is a sidewall sprinkler head?
Sidewall fire sprinklers install along walls or beneath beams where ceiling piping is unavailable, or where aesthetic concerns or obstructions weigh against the use of other sprinkler types. Most are designed to protect small rooms, closets, or hallways and have a semicircular deflector that produces a crescent-shaped spray pattern.
What’s the difference between rated working pressure and testing pressure?
Rated working pressure means pressure under normal conditions.
Testing pressure means pressure for strength test of products.
How to choose the fire sprinkler heads?
The selection and application of sprinkler shall be determined according to the fire risk of the protection place, the building structure of the protection space, the characteristics of the automatic sprinkler system, as well as the flow coefficient, thermal sensitivity index RTI and the maximum protection area of the sprinkler. The fast response sprinkler was first used in residential buildings in the 1970s, and then used in warehouses in the 1980s. Its RTI is less than 50 (m * s)½. The side wall type sprinkler is installed against the wall, which is suitable for installation in places where it is difficult to lay pipes in space. Side wall sprinkler can be used in residential (residential and hotel) and office places with light hazard level and medium hazard level I. Quick response sprinklers should be used in medium and light hazard places and places for life protection, such as public entertainment places, houses, atrium corridors, hospitals, wards and treatment areas of nursing homes, collective activity places for the elderly, children and the disabled, etc. According to the specification, the maximum temperature at the general installation site is 30 ℃ + 30 ℃. Some special places with temperature such as kitchen and boiler room need to use 93℃ (200℉) sprinkler heads.
Product detail pictures:
Related Product Guide:
We always follow the principle Quality Very first, Prestige Supreme. We have been fully committed to delivering our customers with competitively priced high-quality products and solutions, prompt delivery and experienced services for Fire Fighting Eqiupment ZSTX 15-93℃ Side wall Chrome plated Fast response Fire sprinkler heads – Zhurong , The product will supply to all over the world, such as: San Diego, South Korea, Bolivia, Our market share of our products and solutions has greatly increased yearly. If you are interested in any of our products or would like to discuss a custom order, make sure you feel free to contact us. We've been looking forward to forming successful business relationships with new clients around the world in the near future. We've been looking forward to your inquiry and order.