Best quality Fire Sprinkler Glass Bulb - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong
Best quality Fire Sprinkler Glass Bulb - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong Detail:
Size(mm) | Temperature Rating(℃/°F) | Color | |
A | 3.8 | 57℃ / 135°F | orange |
B | 2.02 | 68℃ / 155°F | red |
C | <4.5 | 79℃ / 175°F | yellow |
D | 5±0.1 | 93℃ / 200°F | green |
d1 | 5.3±0.2 | 141℃ / 286°F | blue |
d2 | 5.3±0.3 | ||
L | 24.5±0.5 | ||
l1 | 20±0.4 | ||
l2 | 19.8±0.4 | ||
Glass bulb load(N) | Average Cursh load(X) | 4000 | |
lower Tolerance Limit(TL) | ≥2000 | ||
Maximum clamping torque | 8.0 N·cm | ||
Response time index(m*s)0.5 | 80<RTI≤350 |
As a professional sprinkler bulb manufacturer, MH has its own special R & D team, which is committed to continuously improving the quality and characteristics of products and meeting the needs of various customers, including all the requirements for sprinkler bulbs in GB 16809-2008 for fire windows and GB / T 25205-2010 for shower heads.
Our sprinkler bulb can be applied to almost any place where temperature sensing sprinkler bulb release mechanism is needed, such as kitchen smoke hood, paint spraying room, fire damper, smoke exhaust fan, etc. In order to meet the different needs of our customers for sprinkler bulb size, specification and RTI, we have specially set up a standby assembly line and separate machine production. All products support OEM / ODM.
All sprinkler bulbs will be inspected when leaving the factory, including:
1. Appearance and size
Ensure that the outer surface of all sprinkler bulbs is not damaged, there are no bubbles or other impurities inside the glass material, and the bubble size in the working liquid of sprinkler bulbs of the same specification is uniform. The dimensional deviation of all sprinkler bulbs is within the specified allowable range. The temperature and color of all sprinkler bulbs are easy to identify.
2. Static operating temperature
The static operating temperature of all sprinkler bulbs shall not exceed the following temperature range: X ± (0.035x + 0.62) x refers to the nominal operating temperature, and the unit is Celsius (℃)
3. Crushing load
The average crushing load shall not be lower than the specified value, and the lower limit of crushing load error shall not be lower than 50% of the average crushing load.
Product detail pictures:
Related Product Guide:
Gaining purchaser gratification is our firm's intention eternally. We will make wonderful endeavours to build new and top-quality merchandise, satisfy your exclusive needs and provide you with pre-sale, on-sale and after-sale products and services for Best quality Fire Sprinkler Glass Bulb - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong , The product will supply to all over the world, such as: New York, Southampton, Lahore, For more than ten years experience in this filed, our company has gained high reputation from home and abroad. So we welcome friends from all over the world to come and contact us, not only for business, but also for friendship.
By Murray from Philadelphia - 2017.04.18 16:45
Company director has very rich management experience and strict attitude, sales staff are warm and cheerful, technical staff are professional and responsible,so we have no worry about product,a nice manufacturer.
By Claire from New Zealand - 2017.07.28 15:46